REMKO HEAT PUMP MANAGER

Factory setting

Designation

Day

Time

Is activated in the operating mode

Heating circuit 1

prog 1

Mo.-Fr.

Mo.-Su.

Sa.+Su.

06:00-22:00
06:00-22:00
07:00-23:00

Automatic 1

Heating circuit 1

prog 2

Mo.-Fr.

Mo.-Su.

Sa.+Su.

06:00-08:00, 16:00-22:00
06:00-08:00, 16:00-22:00

07:00-23:00

Automatic 2

Heating circuit 2

prog 1

Mo.-Fr.

Mo.-Su.

Sa.+Su.

06:00-22:00
06:00-22:00
07:00-23:00

Automatic 1

Heating circuit 2

prog 2

Mo.-Fr.

Mo.-Su.

Sa.+Su.

06:00-08:00, 16:00-22:00
06:00-08:00, 16:00-22:00

07:00-23:00

Automatic 2

Hot water

Mo.-Fr.

Mo.-Su.

Sa.+Su.

05:00-21:00
05:00-21:00
06:00-22:00

in all modes except for Stand by

Circulation pro-

gram

Mo.-Fr.

Mo.-Su.

Sa.+Su.

05:00-21:00
05:00-21:00
06:00-22:00

in all modes except for Stand by

WE 1-4 enable

Mo.-Fr.

Mo.-Su.

Sa.+Su.

00:00-24:00
00:00-24:00
00:00-24:00

The heating appliances can only be put into
operation in the enabled times set here.
(A demand for heat from a user or tank must
also exist for a heating appliance to operate)
WE1 = heat pump
WE2 = not used
WE3 = Electric heater or boiler
WE4 = not used .

S-Kick enable

Mo.-Su.

07:00-22:00

Enable time for the solar kick functions
(see specialist

solar MF).

PU night charging

Mo.-Su.

00:00-05:00

The second heating appliances are blocked
for the duration of the enable time set here.
In this time period, the buffer tank is only
warmed by the heat pump to the set tem-
perature (see specialist

heat pump

Min T-PU WE).

PU night charging should not be enabled in
the heating and hot water time periods.

All time programmes can be set here.

Level 4 - TIME PROGRAMME - Description of parameters and settings