7 specifications, 8 setmodes32, 9 getmodes32 – Sensoray 2600 User Manual

Page 47

Advertising
background image

2600 Family Instruction Manual

42

Chapter 7 : Model 2610 Digital I/O Module

All modified outputs will change state
synchronously so that arbitrary groups of DIO
channels can be used in applications that require
“state machine” type behavior.

7.6.8 SetModes32

Function

Programs the operating modes for DIO channels
0 through 31.

Opcode

0x07

Command

(M<7:0>),(M<15:8>),(M<23:16>),

(M<24:31>)

Response

none

Notes

This command is available only on 7410
firmware version 1.02 or higher.

Each of channels 0 through 31 may operate in
either the Standard mode or the PWM mode.
Following a reset, all channels default to the
Standard operating mode.

When a channel’s operating mode is first
changed to the PWM mode, its duty cycle is reset
to zero to force the output off until the duty cycle
is explicitly set by a SetPwmRatio action.

7.6.9 GetModes32

Function

Returns the operating modes for DIO channels 0
through 31.

Opcode

0x08

Command none

Response

(M<7:0>),(M<15:8>),(M<23:16>),

(M<24:31>)

Notes

This command is available only on 7410
firmware version 1.02 or higher.

GetModes

returns the current operating modes

of DIO channels 0-31. The operating modes may
be changed by design (e.g., in response to a
SetModes

action) or unexpectedly (e.g., all

channel operating modes revert to the default
when a module reset occurs).

7.7 Specifications

Parameter

Function

M[]

Operating modes for channels 0 to
31. Each bit is associated with a
channel number. Set a bit to one for
PWM mode, or zero for Standard
mode.

Parameter

Function

M[]

Operating modes for channels 0 to
31. Each bit is associated with a
channel number. Set a bit to one for
PWM mode, or zero for Standard
mode.

Table 20: Model 2610 Specifications

Interlock Power
Daisy Chain

Voltage range

+5.8VDC to +24VDC, as required by DIO channel loads.

Current

10A maximum, per circuit.

DIO

Channels

48

Pull-up resistor

47K ohms, 5%.

On state output current

100mA sink per output, max.
2A total sink (sum of all output currents), max.

Off state output leakage

400µA @ 24V
200µA @ 12V
80µA @ 5V

Mating Connectors
(*) = included with
module

IOM port (qty 1)

RJ-45 plug, AMP 554169 or equivalent

Digital I/O (qty 48)

RJ-12 plug, AMP 520425-3 or equivalent

Power daisy chain (qty 2)

AMP 770849-6 with 640706-1 pin contacts (6), or equivalent Accepts Sensoray cable
assembly, part number 2600C1.

Temperature

Operating temperature

0 to 70°C operating.

Power

Power

+24V @ 120mA, max., with no output current, all output LEDs turned on.

Dimensions

Outer dimensions

5.0H x 14.3W x 2.0D inches, including DIN mounting frame. Depth is specified with respect to
surface of DIN rail support panel; additional clearance required for field wiring.

Advertising