Sensoray 2600 User Manual

Page 73

Advertising
background image

2600 Family Instruction Manual

68

Chapter 11 : Model 2652 SSR Module

Relays

Channels

8, with sockets.

Form factor

Industry standard digital SSRs: 0.6W x 1.7L x 1.25H (inches).

SSR types
(not included with 2652)

Any combination of Grayhill 70- series or equivalent. Examples:
70-OAC24 - 120V AC output
70-OAC24A - 240V AC output
70-ODC24 - 60V DC output
70-ODC24R - mechanical relay output
70-IAC24 - 120V AC input
70-IAC24A - 240V AC input
70-IDC24 - 32V DC input
Note: All of the above SSR types employ 24V logic. Part numbers will be
different for other logic levels. Example: use 70-OAC5 for 120V AC output if
the associated daisy-chained DC power supply is 5V.

Mating Connectors
(*) = included with module

IOM port (qty 1)

RJ-45 plug, AMP 554169 or equivalent.

Relay line/load (qty 16)

(*) AMP 172-166 with 770988-1 socket contacts (2), or equivalent.

Power daisy chain (qty 2)

AMP 770849-6 with 640706-1 pin contacts (6), or equivalent. Accepts
Sensoray cable assembly, part number 2600C1.

Temperature

Operating range

0 to 70°C.

Power

Input power

+24V ±5% @ 310mA, with eight 70-OAC24 SSRs energized.

Dimensions

Outer dimensions

5.0H x 8.6W x 3.0D inches, including relays and DIN mounting frame.
Depth is specified with respect to surface of DIN rail support panel.

Table 37: Model 2652 Specifications