2600 Family Instruction Manual

70

Chapter 12 : Model 2653 SSR Module

Figure 63: Pinouts of Connectors P33 and P34

The external DC power sources need not be derived from
interlock contacts, but by employing interlocked power
sources, the system interlock cabling can be minimized. This
feature is especially useful for guaranteeing the fail-safe
shutdown of select SSR channels in the event of a critical
condition such as emergency stop (ESTOP) activation, open
safety hood, etc.

Figure 64 illustrates a system in which PWR0 is connected to
multiple system emergency stop contacts, and PWR1 is routed
through a safety hood interlock contact. Note that all of the
external power sources are daisy-chained from module to
module. Any SSR that is configured to use PWR0 will
automatically lose power when either ESTOP contact is
opened, and any SSR that is configured to use PWR1 will lose
power when the hood opens. All other SSRs use the +24V
“always on” power source and thus are unaffected by interlock
contacts. PWR2, PWR3 and PWR4 are not used in this
application.

Figure 64: Wiring Example With Interlock Contacts

Use Sensoray cable assembly, part number 2600C1, to connect
P1 or P2 to the power daisy chain

12.2.3 Relay Power Selection Shunt

Each relay channel may be independently operated from any of
the six external DC power sources (that are connected to P33
and P34) by installing the appropriate programming shunt.

A shunt receptacle matrix is provided for each channel. Each
matrix has six shunt positions, corresponding to the six
external DC power sources. As shown in Table 38, a 2mm
programming shunt (supplied with the 2653) must be installed
at the position corresponding to the relay channel’s target
power source. Only one shunt should be installed per matrix.

Each channel’s shunt receptacle matrix is located adjacent to
its SSR socket as shown in Figure 65.

Figure 65: SSR Channel Layout (top view)

12.2.4 I/O Connectors

The 2653 module employs thirty two connectors for field
wiring. Each channel uses one connector for line and one for
load (see Figure 65).

2653

P34

6 - PWR4

5 - PWR3

4 - PWR2

2 - PWR0

1 - +24V

3 - PWR1

Name Pin

Function

+24V

1

+24V power, always on.

PWR0

2

Optional positive DC power #0.

PWR1

3

Optional positive DC power #1.

PWR2

4

Optional positive DC power #2.

PWR3

5

Optional positive DC power #3.

PWR4

6

Optional positive DC power #4.

(top view)

P33

PWR4

PWR3

PWR2

PWR1

PWR0

+24V

2601 MM

TBLK
@J22

P1

P33

P34

2653 SSR

To
Other
IOMs

+24V

ESTOP

SW1

ESTOP

SW2

HOOD

INTERLOCK

Table 38: Interlock Power Programming Matrix

PWB

Label

Shunt

Pins

Selected Power Source

+24V

1-2

+24V power, always on (default)

0

3-4

Optional positive DC power #0.

1

5-6

Optional positive DC power #1.

2

7-8

Optional positive DC power #2.

3

9-10

Optional positive DC power #3.

4

11-12

Optional positive DC power #4.

Table 39: Line and Load Connectors

Relay

Channel

Connector

Line

Load

CH0

P2

P1

CH1

P4

P3

CH2

P6

P5

CH3

P8

P7

CH4

P10

P9

CH5

P12

P11

CH6

P14

P13

CH7

P16

P15

SSR

12

10

8

6

4

2

11

9

7

5

3

1

+24V-
PWR0-
PWR1-
PWR2-
PWR3-
PWR4-

Indicator lights when relay is energized

Line+

Line

Load

Line-

Load-

Load+

Power Programming Matrix