21

©2013 Magnum Energy, Inc.

3.0 Setup

Table 3-4, Battery Type to Charge Voltages

Battery

Type

Inverter

Voltage

Absorption

Voltage

Float

Voltage

Equalization

Voltage

GEL

12 VDC

14.1 VDC

13.6 VDC

14.1 VDC

1

24 VDC

28.2 VDC

27.2 VDC

28.2 VDC

1

48 VDC

56.4 VDC

54.4 VDC

56.4 VDC

1

Flooded

12 VDC

14.6 VDC

13.4 VDC

15.5 VDC

24 VDC

29.2 VDC

26.8 VDC

31.0 VDC

48 VDC

58.4 VDC

53.6 VDC

62.0 VDC

AGM 1

2

12 VDC

14.3 VDC

13.1 VDC

15.5 VDC

24 VDC

28.6 VDC

26.2 VDC

31.0 VDC

48 VDC

57.2 VDC

52.4 VDC

62.0 VDC

AGM 2

3

12 VDC

14.5 VDC

13.5 VDC

14.5 VDC

1

24 VDC

29.0 VDC

27.0 VDC

29.0 VDC

1

48 VDC

58.0 VDC

54.0 VDC

58.0 VDC

1

Note¹: Voltage same as absorption voltage—to prevent equalization.
Note²: Charge voltages for Concord (Lifeline Series) AGM batteries.
Note³: Charge voltages for East Penn, Deka, Discover and Trojan AGM batteries.

◊ Battery Type (CC/CV) –

The CC/CV selection provides a Constant

Current/Constant Voltage (CC/CV) charging method with an adjustable

charge voltage and a setting that limits output current—if needed. It

consolidates all the battery charge settings that are required for a 2-stage

charging cycle (i.e., Constant Current and Constant Voltage).

Note: The CC/CV settings only display if CC/CV has been selected from

the 04 Battery Type menu

.

Info: If 04 Battery Type is set to CC/CV, the following menus are

no longer accessible and display “CC/CV Controlled” when selected:

03 Absorb Time, 05 Charge Rate, and 09 Final Charge. This is to

prevent charging confl icts that could occur while in the CC/CV profi le.

Max Amps – Sets the maximum charge amperage allowed to charge

the batteries during the CC/CV charge cycles. The range of settings

are provided to limit the charge current to the battery bank, which

helps prevent battery overheating caused by charging at too high a

charge rate.
Default: 200 ADC
Range: 20 - 990 ADC

Chg Volts – Sets the voltage level at which the charger will hold

the batteries during the Constant Voltage cycle.
Default:

13.8 VDC (12v), 27.6 VDC (24v), 55.2 VDC (48v)

Range: OFF, 12.0-16.0 VDC (12v), 24.0-32.0 VDC (24v), 48.0-64.0

VDC (48v)

Info: The voltage settings shown in Table 3-4 are based on the Bat-

tery Temperature Sensor (BTS) at a temperature of 77° F (25° C),

or not connected. If the BTS is connected, the actual charge voltage

will increase if the temperature around the BTS is below 77° F (25°

C), and decrease if higher than 77° F (25° C). This ensures the bat-

teries receive the correct charge voltage regardless of temperature.