2 stacking fault messages, Stack mode fault settings/info, Stackphase fault settings/info – Magnum Energy ME-RC Remote User Manual

Page 59: Stackclock fault settings/info, 0 operation

Advertising
background image

©2013 Magnum Energy, Inc.

52

5.0 Operation

Stack Mode Fault appears on the

LCD. The FAULT (red) LED is on. The

PWR (green), CHG (green), and INV

(green) LEDs are off.

FAULT

PWR

CHG

INV

Stack Mode Fault

Settings/Info..

Figure 5-33, Stack Mode Fault

StackPhase Fault appears on the

LCD. The FAULT (red) LED is on. The

PWR (green), CHG (green), and INV

(green) LEDs are off.

FAULT

PWR

CHG

INV

StackPhase Fault

Settings/Info..

Figure 5-34, StackPhase Fault

• Stack

Mode

Fault

This unit has detected a problem with the “other”

stacked inverter. Check that unit for a fault condition.

Remedy: This fault will automatically clear when the fault with the

other inverter is corrected.

• StackPhase

Fault

1. The AC input wiring is incorrect; 2. One phase

was lost from the AC input source; 3. One of the inverter’s internal transfer

relays is bad; or, 4. The inverter’s AC input circuit breaker may be open.

Remedy: If this fault doesn’t clear after checking these four recom-

mendations, perform an inverter reset (see Section 6.2).

• StackClock

Fault

– There is a stacker cable problem; or, one inverter

is losing synchronization with the other inverter.

Remedy: Ensure you are using a Magnum Stacking Cable (this is

not a telephone/data cable, this is a custom made cable). Inspect

the stacker cable and reconnect at both ends (listen and make sure

you hear an audible “click” from the connectors at both inverters).
Info: This fault has been known to occur when a Magnum Energy

accessory is plugged into the inverter’s Stack port, but the instal-

lation is not using multiple inverters in a stacked confi guration. If

this occurs, perform an inverter reset (see Section 6.2).

FAULT

PWR

CHG

INV

StackClock Fault

Settings/Info..

Figure 5-32, StackClock Fault

StackClock Fault appears on the

LCD. The FAULT (red) LED is on. The

PWR (green), CHG (green), and INV

(green) LEDs are off.

5.3.3.2 Stacking Fault Messages
A fault condition may occur when two inverters are stacked in series—using

the stacking interface—that is not possible on a single inverter installation.

Refer to the following fault messages to help troubleshoot the inverters.

Advertising