7.0 Using an AGS Module: Operating/Monitoring

65

©2013 Magnum Energy, Inc.

To manually stop the generator (only if autostarted by AGS):
1. Press the AGS button. The 01 AGS Control menu displays.
2. Press the SELECT knob. The current gen control setting displays with an

arrow to the right.

3. Turn the SELECT knob to the AGS = OFF setting.
4. Press the SELECT knob again to select this setting. The selection arrow

appears to the right of the screen and the display returns to the 01 AGS

Control menu. The generator should stop at this time.

If the generator does not stop as expected, refer to your AGS Owner’s

Manual.

Autostop Conditions

03 Run Time Hour (page 59)

07 Quiet Time (page 61)

Autostart Conditions

04 Start Temp F (pages 59-60)

05 Start Volts (pages 60-61)

7.4

Enabling the ME-AGS-N using the ME-RC

Before the AGS can begin operating/monitoring for an autostart condition

(using the active AGS settings in the ME-RC remote), it must be enabled.
To enable the AGS:
1. Press the AGS button. The 01 AGS Control menu displays.
2. Press the SELECT knob. The current gen control setting displays with an

arrow to the right.

3. Turn the SELECT knob to the AGS = Enable setting (or to Enable w/QT).
4. Press the SELECT knob again to select this setting. The selection arrow

appears to the right of the screen.

The AGS is now ready to automatically start/stop the generator once an

autostart condition is satisfi ed.
Note: If power is lost to the remote, the AGS control setting returns to the

default OFF setting. Once power is restored, you must enable the AGS again.
Note:
Despite enabling the AGS, you must check the AGS’s current status

and ensure the status displays as “Ready”.

7.5

Starting/Stopping the Generator using ME-RC

The generator can be manually stopped, as well as autostarted/autostopped

using the available settings from your ME-RC.
To autostart/autostop the generator:
In order for the generator to autostart/autostop, one or more of the following

autostart/autostop conditions must be pre-set:

Press the ME-RC’s TECH button, and then rotate and press the SELECT knob

to access the following menus:
TECH: 01 Temperatures Menu (AGS)
This read-only menu displays the ambient temperature reading of the AGS’s

temperature sensor (if installed).
Note: This AGS temperature meter displays the same info as the AGS: 08

AGS TECH menu’s Temp meter (see info for this meter on previous page).

TECH: 02 Revisions Menu (AGS)
This read-only menu displays the fi rmware revision level of the AGS module

that is installed and networked.