7.0 Using an AGS Module: Operating/Monitoring

69

©2013 Magnum Energy, Inc.

7.7.2 AGS Remote Start Statuses

The following “Start” statuses identify the condition that autostarted the

generator. If you determine that the autostart condition occurred sooner

than expected (or didn’t want this autostart condition), refer to the Setup

section for that condition to change (or defeat) the autostart setting.

STATUS

DESCRIPTION

Start Temp

The generator has started based on the AGS: 04 Start

Temp F setting.

Start Test

The AGS is in Test mode. Test mode may be started from

the red TEST button located on the AGS or by selecting

Test” from the AGS: 01 AGS Control menu (refer to your

AGS Owner’s Manual for further information).

Start VDC

The generator has started based on the AGS: 05 Start

Volts setting.

Table 7-4, AGS Remote Start Statuses

7.7.3 AGS Remote Fault Statuses

The following “Fault” statuses indicate that the generator wasn’t able to start

based on an expected autostart condition. Refer to Section 7.8.3 “Resolving

Fault Statuses” for help in diagnosing the problem.

STATUS

DESCRIPTION

Fault Gen Run

The generator stopped before the autostop condition

was satisfi ed.

Fault Temp

The generator failed the autostart cycle in Start Temp

mode.

Fault Test

The generator failed the autostart cycle in Test mode.

Fault VDC

The generator failed the autostart cycle in Start VDC

mode.

Table 7-5, AGS Remote Fault Statuses

7.7.4 General AGS Operational Notes

• If a fault condition occurs, select the OFF setting from the 01 AGS

Control menu, and then select Enable or Test. If the problem persists,

refer to

your AGS Owner’s Manual.

• When the gen control setting in the remote is in the OFF position,

all generator autostart functions are disabled and the AGS module’s

STATUS indicator will also be off.

When AGS control is set to Enabled and an autostart condition occurs,

it attempts an automatic generator start. This is done by closing its

internal relays (based on the Gen Type selection) to control the starter—

much like a person does when manually starting the generator. The

starter is turned on for short periods of time and then turned off. If the

AGS determines that the engine has started while cranking (STATUS

indicator lights solid green), the starter is turned off after a short delay.

If the engine does not start, another attempt is made to turn on the

starter after a long delay period. This is repeated until the generator