4 how to clear ags faults, 0 using an ags module: troubleshooting – Magnum Energy ME-RC Remote User Manual

Page 79

Advertising
background image

7.0 Using an AGS Module: Troubleshooting

©2013 Magnum Energy, Inc.

72

Fault Gen Run – The generator successfully started and ran for more than

two minutes, but the generator unexpectedly stopped by itself before the

active AGS autostop condition was fi nished.

Info: The AGS module determines the generator is running by

monitoring the gen run sense voltage/signal. When this gen run

sense voltage/signal is no longer available, the AGS thinks the gen

is off or has stopped.

Info: Gen run fault detection is not active if the generator is manu-

ally started.

Remedy:
A.
If the generator is still running: Confi rm you are getting the cor-

rect gen run sense signal to the AGS module. For further assistance,

refer to your AGS Owner’s Manual.
B. If the generator is not running: Check the generator for fault

codes and adequate fuel. If neither is an issue, check the genera-

tor’s owner’s manual for troubleshooting tips to determine why it

may have shut down on its own.

7.8.4 How to Clear AGS Faults

Go to the AGS: 01 AGS Control menu and select AGS= OFF.
Note: After the fault clears and the reason for the fault is determined, be

sure to re-enable the AGS to autostart. Go to the AGS: 01 AGS Control menu

and select AGS= Enable or AGS= Enable w/QT.
Once the fault is cleared and the reason for the fault is determined, you

should re-enable the AGS to see if the fault returns, or test the AGS/

generator system by performing the AGS Functional Test for your remote

(see your AGS Owner’s Manual).

Advertising