J. install metal roof flashing – Heat & Glo Fireplace Heat & Glo 350TRSILP-AUF User Manual

Page 50

Advertising
background image

Heat & Glo • 350TRSI-AUF, 350TRSILP-AUF • 2089-980 Rev. R • 2/13

50

J. Install Metal Roof Flashing

• See minimum vent heights for various pitched roofs

(Figure 10.19) to determine the length of pipe to extend

through the roof.

• Slide the roof flashing over the pipe sections extending

through the roof as shown in Figure 10.20.

Figure 10.19 Minimum Height From Roof To Lowest Discharge

Opening

NOTICE: Failure to properly caulk the roof flashing and

pipe seams may permit entry of water.
• Caulk the gap between the roof flashing and the outside

diameter of the pipe.

• Caulk the perimeter of the flashing where it contacts the

roof surface. See Figure 10.20.

• Caulk the overlap seam of any exposed pipe sections

that are located above the roof line.

H (MIN.) - MINIMUM HEIGHT FROM ROOF

TO LOWEST DISCHARGE OPENING

VERTICAL

WALL

TERMINATION

CAP

HORIZONTAL

OVERHANG

305 mm

X

ROOF PITCH

IS X/ 305 mm

LOWEST

DISCHARGE

OPENING

510 mm MIN.

610 mm MIN.

Angle

H (Min.) mm

0°-26.6° .......................................................... 500*
26.6°-30.3° .......................................................... 500*
30.3°-33.7° .......................................................... 500*
33.7°-36.9° .......................................................... 610*
36.9°-39.8° .......................................................... 760
39.8°-42.5° .......................................................... 990
42.5°-45.0° ........................................................1 220
45.0°-49.4° ........................................................1 520
49.4°-53.1° ........................................................1 830
53.1°-56.3° ........................................................2 130
56.3°-59.0° ........................................................2 290
59.0°-60.3° ........................................................2 440

Important Notice: Heat shields may not be field constructed.

I. Heat Shield Requirements for Horizontal

Termination

WARNING! Risk of Fire! To prevent overheating and fire,

heat shields must extend through the entire wall thick-

ness.

DO NOT remove the heat shields attached to the

wall shield firestop and the horizontal termination cap

(shown in Figure 10.18).

• Heat shields must overlap 1-1/2 in. (38 mm) mini-

mum.

There are two sections of the heat shield. One section

is factory-attached to the wall shield firestop. The other

section is factory-attached to the cap. See Figure 10.18.
If the wall thickness does not allow the required 1-1/2 in.

(38 mm) heat shield overlap when installed, an extended

heat shield must be used.
• If the wall thickness is less than 4 in. (102 mm) (DVP)

or 4-3/8 in. (111 mm) (SLP), the heat shields on the cap

and wall shield firestop must be trimmed. A minimum

1-1/2 in. (38 mm) overlap MUST be maintained.

• Use an extended heat shield if the finished wall

thickness is greater than 7-1/4 in. (184 mm).

• The extended heat shield may need to be cut to length

maintaining sufficient length for a 1-1/2 in. (38 mm)

overlap between heat shields.

• Attach the extended heat shield to either of the existing

heat shields using the screws supplied with the extended

heat shield. Refer to vent components diagrams in the

back of this manual.

• Rest the small leg on the extended heat shield on top

of the pipe section to properly space it from the pipe

section.

Advertising
This manual is related to the following products: