Table 5-3

AG_RECV / AG_LRECV Codes

NDR

Meaning

STATUS

ERROR

0

1

8304

H

The connection is not established. The send job should only be
attempted again after waiting for at least 100 ms.

0

1

8F23

H

Source area invalid, for example:

Area does note exist in the DB.

0

1

8F25

H

Area error writing a parameter.

0

1

8F29

H

Alignment error writing a parameter.

0

1

8F30

H

Parameter is in the write-protected 1st act. data block.

0

1

8F31

H

Parameter is in the write-protected 2nd act. data block.

0

1

8F32

H

Parameter contains a DB number that is too high.

0

1

8F33

H

DB number error.

0

1

8F3A

H

Destination area not loaded (DB).

0

1

8F43

H

Timeout writing a parameter to the I/O area.

0

1

8F45

H

Address of the parameter to be read is disabled in the access
track.

0

1

8F7F

H

Internal error, e.g. illegal ANY reference.

0

1

8090

H

No module with this address exists or the CPU is in the STOP
mode.

0

1

8091

H

Logical base address not at a double word boundary.

0

1

8092

H

In the ANY reference, a type other than BYTE is specified.
(S7-400 only)

0

1

80A0

H

Negative acknowledgment reading from the module.

0

1

80A4

H

The communication bus connection between the CPU and CP is
not established.

0

1

80B0

H

The module does not recognize the data record.

0

1

80B1

H

Destination area invalid.

0

1

80B2

H

The communication bus connection between the CPU and CP is
not established.

0

1

80C0

H

The data record cannot be read.

0

1

80C1

H

The specified data record is currently being processed.

0

1

80C2

H

There are too many jobs pending.

0

1

80C3

H

CPU resources (memory) occupied.

0

1

80C4

H

Communication error (occurs temporarily and a repetition in the
user program will often remedy the problem).

0

1

80D2

H

Module base address incorrect.