Communication via Ethernet CPs in S7 Stations

30

SIMATIC NET NCM S7 for Industrial Ethernet

C79000-G8976-C129–06

1.6

FETCH/WRITE Services (Server)

Application

In addition to the SEND/RECEIVE interface, the FETCH/WRITE functionality
provides further services for S5-compatible communication on configured transport
connections.

The FETCH/WRITE interface is used primarily to attach SIMATIC S7 to SIMATIC
S5 and to other non-S7 stations (for example PCs).

S

FETCH

The partner on the connection (SIMATIC S5 or non-S7 station) can read
system data on the SIMATIC S7 PLC.

S

WRITE

The partner on the connection (SIMATIC S5 or non-S7 station) can write
system data on the SIMATIC S7 PLC.

From the point of view of the SIMATIC S7 PLC, this is a passive communication
function; the communications partner initiates the connection establishment.

For further information, refer to the system documentation of the SIMATIC S5 PLC
or the non-S7 station you are using.

Connection Types

To access a station with FETCH or WRITE functions, a FETCH passive or WRITE
passive connection must be configured. The following types are possible:

S

ISO Transport

S

ISO-on-TCP

S

TCP

Coordinating Access Using the User Program

To coordinate access, you can use the FCs AG_LOCK and AG_UNLOCK.

With these FCs, you can coordinate access to system memory areas so that no
inconsistent data are created and transferred.

SIMATIC S5

On the SIMATIC S5 station, the FETCH/WRITE services are configured and
started by READ ACTIVE/PASSIVE and WRITE ACTIVE/PASSIVE.