Configuring Communication Connections

87

SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06

4.3

Connections

Characteristics of a Connection

A communication connection allows program-controlled communication between
two nodes on Industrial Ethernet with the following characteristics:

S

The data transfer is bi-directional, in other words, it is possible to transmit and
receive on the connection simultaneously.

S

Both stations have the same rights, in other words, each station can trigger the
send and receive procedures in response to events.

S

The address of the communication partner is specified in the configuration.

The free UDP connection is the exception to this. Here, the address is specified
at the FC interface in the user program.

Communication
connection

Ethernet CP

Ethernet
node

SIMATIC S7 station
with Ethernet CP

receive

send

receive

send

Ethernet
node

receive

send

receive

send

Communication
connection

Figure 4-3

Sending and Receiving via one Communication Connection

Note

The term “connection” is also used here for UDP. Reason: during configuration
(just as in TCP) the communication partners are assigned to each other and
therefore logically “connected”. In actual fact, with UDP there is no explicit
connection establishment between communication partners.