Siemens Simantic Net NCM for Industrial Ethernet S7 User Manual

Page 25

Advertising
background image

Communication via Ethernet CPs in S7 Stations

25

SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06

Configuring S7 Connections

Create S7 connections to use S7 communication for data exchange between two
SIMATIC S7 stations.

For more detailed information, refer to the STEP 7 Description /6/ /8/.

Notice

S7 connections via routers are supported only within a STEP 7 project but not bet-
ween partners in different STEP 7 projects of a multiproject!

Interface in the User Program of the S7 Station

You use SFBs (for S7-400) and FBs (for S7-300) in the user program.

Block type

1)

Client

Server

Described in

SFB / FB12

BSEND

x

STEP 7
D

t ti

/9/

SFB / FB13

BRCV

x

Documentation /9/

SFB / FB15

PUT

x

1)

SFB / FB14

GET

x

1)

SFB / FB8

USEND

x

SFB / FB9

URCV

x

SFC / FC62

CONTROL (S7-400) /
C_CNTRL (S7-300)

x

x

2)

1) you do not need to configure a connection on the server

2) for S7-300

Notice

Please remember the following points regarding data consistency in your user pro-
gram:

In the CPU of the S7 station, the read or written information is taken from the S7
user program into the operating system or copied from the operating system to the
S7 user program in blocks of 8 or 32 bytes (depending on the firmware version).

If information in the word or double-word format is located across such bounda-
ries, data inconsistency may arise during transmission using S7 communication!

For more detailed information, refer to the STEP 7 documentation /9/.