1 checklist for general cp functions – Siemens Simantic Net NCM for Industrial Ethernet S7 User Manual

Page 189

Advertising
background image

NCM S7 Diagnostics

189

SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06

6.6.1

Checklist for General CP Functions

Table 6-5

Checklist for Typical Problems When Operating a CP in a System

Problem

Possible Cause

Identifying the Cause and Remedy

The Ethernet CP will not
change to the RUN mode.

Invalid configuration
loaded on the Ethernet
CP.

Yellow STOP LED and red SF LED lit
continuously.

Call up the diagnostic buffer in NCM S7
Ethernet Diagnostics.

Example of an entry

CP STOP due to invalid CP parameter
assignment

What to do:
Correct the configuration of the Ethernet CP.

Switch set to STOP on the
Ethernet CP.

Query the operating mode in NCM S7
Diagnostics.

Operating mode: STOP, Cause: switch set to
STOP

What to do:
Change the switch to RUN on the Ethernet CP

Advertising