Linking to Other Systems with FETCH/WRITE

214

SIMATIC NET NCM S7 for Industrial Ethernet

C79000-G8976-C129–06

Parameter Values

S7 Address Area

DB

M

I

Q

ORG ID

01

H

02

H

03

H

04

H

Source/dest.
data from/to
data block in
main memory

Source/dest.
data from/to
flag area

Source/dest.
data from/to
process
image of the
inputs (PII)

Source/dest.
data from/to
process
image of the
outputs (PIQ)

DBNR

DB, from
which the
source data
are taken or
to which the
dest data are
transferred

irrelevant

irrelevant

irrelevant

permitted range

1...255

Start address

DW number,
from which
the data are
taken or
written to

Flag byte no.,
from which
the data are
taken or
written to

Input byte no.,
from which
the data are
taken or
written to

Output byte
no., from
which the
data are
taken or
written to

permitted range

0...2047

0...255

0...127

0...127

Length

Length of the
source/dest.
data field in
words

Length of the
source/dest.
data field in
bytes

Length of the
source/dest.
data field in
bytes

Length of the
source/dest.
data field in
bytes

permitted range

1...2048

1...256

1...128

1...128