SEND/RECEIVE Interface in the User Program

74

SIMATIC NET NCM S7 for Industrial Ethernet

C79000-G8976-C129–06

3.1

How the SEND/RECEIVE Interface Works on the CPU

Functions (FCs)

The following functions (FCs) are available for handling communication on
connections:

S

AG_SEND/AG_LSEND
This block takes the user data from the specified user data area and transfers it
to the Ethernet CP.

S

AG_RECV/AG_LRECV
This block transfers received user data to the user data area specified in the
call.

The diagram below illustrates the situation. Using the FCs AG_SEND/AG_LSEND
and AG_RECV/AG_LRECV, the user program instructs the Ethernet CP to send or
receive data on the configured connection.

Communication
connection

Ethernet CP

CPU

STEP 7
user program

User data
buffer

CP
database

Ethernet station SIMATIC S7

receive

send

User data
areas

AG_RECV

AG_SEND

Figure 3-1

Interaction of the CPU and Ethernet CP on Connections

Amounts of Data

The Ethernet CP can transfer the amounts of data shown in the table below per job
on one connection:

Table 3-1

ISO Transport

ISO-on-TCP

TCP

UDP

Sending

8192 bytes

8192 bytes

8192 bytes

2048 bytes

Receiving

8192 bytes

8192 bytes

8192 bytes

2048 bytes