background image

Programming FCs (Functions) and FBs for S7 Ethernet CPs

168

SIMATIC NET NCM S7 for Industrial Ethernet

C79000-G8976-C129–06

User program
(CPU cycle)

Ethernet CP

Communications Partner

LOCKED = 0

LOCKED = 0

AG_LOCK

AG_LOCK

AG_LOCK

LOCKED = 1

FETCH/WRITE
access to DB x
active

FETCH/WRITE
access to DB x
active

Time

Time

Time

Data

processing

in DB x

FETCH/WRITE

FETCH/WRITE rejected

AG_UNLOCK

STATUS = 700x

Cycle n

Cycle n+1

Cycle n+2

Cycle n+m

...

The lock job must first be monitored in the user program using the code in the
return parameter LOCKED. As long as LOCKED=0 is indicated, it must be
assumed that there is still a FETCH/WRITE access active.

If LOCKED=1 is indicated, this shows that the lock is active; data can now be
modified by the user program.

The status code is updated at each block call.