background image

Communication via Ethernet CPs in S7 Stations

23

SIMATIC NET NCM S7 for Industrial Ethernet
C79000-G8976-C129–06

1.4

S7 Communication on Industrial Ethernet

Application

S7 communication via Industrial Ethernet allows program-controlled
communication using communication SFBs/FBs via configured S7 connections.
Per job, up to 64 Kbytes of user data can be transmitted.

The Ethernet CP acts as an “S7 communication relay” by passing on the S7
functions via Industrial Ethernet (see /8/). Depending on the configuration of the
Ethernet CP, data transfer is on the basis of the ISO transport or the ISO-on-TCP
protocol (TCP/IP with RFC 1006).

From the perspective of the user, S7 communication is identical over PROFIBUS
and Industrial Ethernet.

Nodes

Two cases can be distinguished depending on device type and plant configuration:

S

Client and server functionality at both ends

S7 connections can be operated between the following nodes with the entire
functionality of S7 communication:

– between S7 stations S7-300 and S7-400;

– between S7 stations and PC/PG stations with an Ethernet CP.

Ethernet

PC/PG with Ethernet CP

S7 – 400

S7 – 300

Ethernet CP

M7

* only TCP/IP

S7 – 300 / 400

Ethernet CP

PUT / GET
BSEND / BRECV
USEND / URECV

WAN *

Figure 1-3

Nodes Communicating on S7 Connections over Industrial Ethernet