8

1.6

Power Cables

The cable design must comply with the voltages and currents provided in this section, follow local wir-

ing practices and take into consideration the environmental conditions (temperature and physical

support media).
For cable entry terminal, refer to Figure 22.

!

WARNING

Before starting the UPS, ensure that you are aware of the location and operation of the

external isolators that connect the ups input/bypass supply to the mains distribution panel.
Check that these supplies are electrically isolated and post any necessary warning signs to

prevent their inadvertent operation.

!

WARNING

Failure to follow adequate earthing procedures may result in electromagnetic interference or

in hazards involving electric shock and fire.

Table 1

Maximum steady state AC and DC currents

UPS

Rating

(kVA)

Nominal Current, Amps

Busbar Stud Size

Input Mains Current

1,2

With Full Battery

Recharge

3ph + N

Output Current

2

at Full Load

3ph + N

Battery at

End of

Discharge

Input/Output/

Bypass

Cables

External

battery

Cables

(Bolts)

Torque

Load

(Nm)

380V

400V

415V

380V 400V 415V

Bolt

Hole

Dia.

(mm)

10

22

21

20

15

14

13

22

M6

6

M6

5

15

33

32

31

22

21

20

33

20

44

43

42

30

29

28

44

30

63

62

61

45

44

42

66

1. Input mains current listed for common rectifier and bypass AC input. For split input the rectifier current is 94% of the currents

listed.

2. Non-linear loads (switch mode power supplies) affect the design of the output and bypass neutral cables. The current

circulating in the neutral cable may exceed the nominal phase current. A typical value is 1.5 In.

3. Protective earth cable: Connect each cabinet to the main ground system must follow the most direct route possible.

The earth conductor shall be sized in accordance with the AC supply fault rating, cable lengths and type of protection. Typical
cross sectional areas are 2.5mm

2

(10kVA), 6mm

2

(15kVA), 10mm

2

(20kVA), 16mm2 (30kVA), as per AS / IEC 60950-1

4. When sizing battery cables, a maximum volt drop of 4 VDC is permissible at the current ratings given in Table 1. The load

equipment is generally connected to a distribution board containing individually protected busbars rather than connected
directly to the UPS output. The output cables from paralleled units to the parallel distribution bus should be of same length so
as to optimise the sharing of current. Do not form coils, so as to minimise the formation of electromagnetic interference.

5. For terminal location – refer to 4.0 - Installation Drawings)

Table 2

Distance from floor to connection point on the equipment

UPS

Minimum Distance

mm (in.)

Rectifier A.C. Input supply

284 (11-1/5)

Bypass A.C. Input supply

284 (11-1/5)

UPS Output A.C.

369 (14-1/2)

Battery Power

369 (14-1/2)

Auxiliary cables: Monitor board (U2)

1104 (43-1/2)