Battery Installation

20

2.3.6 Battery Temperature Sensor (Optional)

The optional external battery temperature sensor kit contains one probe and one temperature trans-

port board as illustrated in Figure 7. It is connected to the UPS Monitor Board.

Figure 7

Single temperature sensor and monitor board-U2

2.3.7 Moving the Battery Cabinets

Ensure that the weight is within the designated surface weight loading of any handling equipment.

See Table 8 for weight details.
Battery cabinets can be handled by means of a fork lift or similar equipment.

Seismic anchors option is available for anchoring the unit to a concrete floor.

2.3.8 Cable Entry

Cables enter the battery cabinet from the bottom. Cable entry is made possible by removing a blank-

ing piece fitted at the bottom to reveal the cable entry hole.

!

WARNING

Ensure any lifting equipment used in moving the cabinet has sufficient lifting capacity.

NOTE
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a

minimum.
When the equipment has been finally positioned ensure the adjustable feet are set so that the

battery cabinet will remain stationary and stable.

Temperature

Sensor

TMP-2

+

IN

-

NC

12V

GND

OUT

UPS

Monitor

Board

– U2

X7

-12V

GND

BAT-T

Cable W2 is packed with the temperature sensor.

Name: W2 L=5m

Name: W1 L=30m