Single Module UPS Installation

12

1.8

Dry Contacts

The UPS provides input dry contacts and output dry contacts.

1.8.1 Input Dry Contacts

There are several input dry contacts at the X3 slot.

Figure 3

Input dry contacts

X3 Ancillary Control and Alarms

X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts
The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, push-in ter-

minal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS when

connection between the relevant terminal and the +12V terminal is altered. Cables connected to X3 IN

DRY must be segregated from power circuits (for screening purposes), double insulated and of a typical 0.5

to 1mm

2

cross-section area for maximum runs between 25 and 50 meters (82-164 ft), respectively.

1.8.2 Maintenance Bypass Cabinet Interface

J26 and J30 are the MBC interface.

Table 3

Input dry contacts at X3

Position

Name

Description

J4.1

ENV

3

Battery Room Alarm (NC)

J4.2

BtG

Battery Ground Fault Detection (NC)

J4.3

GEN

1,2

On Generator (NO)

J4.4

+12V

+12V Power

1 - Must be configured by configuration software before becoming active.
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).
3 - Activating this feature turns the battery charger off.

Table 4

Maintenance bypass cabinet interface

Position

Name

Description

J26.1

T_IT

1

Input transformer overtemperature (NC)

J26.2

AUX_I

Reserved

J26.3

+12V

+12V Power

J26.4

GND

Power Ground

J30.1

FUSE

Reserved

J30.2

F_FAN

Fan Fail Alarm (NC)

J30.3

T_OT

1

Output Transformer Overtemperature (NC)

J30.4

AUX_O

Reserved

1

- Must be configured by software before becoming active

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm

2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.