Options—For Assembly Inside the UPS Cabinet

66

8.0

O

PTIONS

—F

OR

A

SSEMBLY

I

NSIDE

THE

UPS C

ABINET

Several items of optional equipment are available for connection to the Liebert NX UPS. These are

described in this section of the manual and should be fitted prior to installation.

8.1

Protection

8.1.1 Battery Ground Fault Detection

In addition to any residual current device mounted externally and upstream the UPS or when

optional isolation transformers are fitted to the UPS, an optional residual battery current device can

be fitted to detect leakage current from the battery into the PE (Protective Earth) Residual current

range monitored: 30~3000mA.
Power supply voltage for the set: AC230V (L-N);
When a battery ground fault is detected, an alarm will appear on the UPS display panel.
An additional Dry contact fault Alarm signal is available for remote monitoring:

The Battery ground fault detection set contains one CT (current transformer) and one DC sensitive

residual current monitor. The connection of this set for UPS is illustrated as follows.

Figure 36 Battery ground fault detection set connections

Table 24

Dry contact fault alarm signal is available for remote monitoring

Terminal

Name

Definition

21

Common

Battery Ground Fault Detection – can be

programmed as Alarm or Pre-Alarm

22

NC

24

NO

BCB or

Contactor

Battery

Socket

Output
Phase

Output
Neutral

Current Transformer
W1-A358 (installed
externally only )

Monitor Board

-U2

UPS

IN DRY-X3

+12V

BtG

Battery Ground
Fault Detection
Resys B470
(AC230)

11

14

A1

A2

K1 K2

I2

I2

4

2

Batt +

Batt -

Batt-N

X

X