5 emergency power off input, Table 7 epo input contact relays, X5: auxiliary dc power output – Liebert Emerson NX UPS System User Manual

Page 23: X6: analog input interface, Emergency power off input, Table 7, Epo input contact relays

Advertising
background image

Single Module UPS Installation

15

1.8.5 Emergency Power Off Input

The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel

or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 5, is the remote EPO input interface. The EPO has an NO/NC contact

point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1
If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the

auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop

switch between these two terminals using shielded cable (see Figure 5 and Table 7). If this function

is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.

X5: Auxiliary DC Power Output

Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maxi-

mum current is 500mA.

X6: Analog Input Interface

Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.

• X6 pin 1: Not used
• X6 pin 2: +12V
• X6 pin 3: ENV-T – environment temperature detection
• X6 pin 4: GND

X7: External Battery Temperature Detector Interface

Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see

Figure 7).
Pin reference:

• X7 pin 1: Not used
• X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)
• X7 pin 3: BAT-T (Battery Temperature signal)
• X7 pin 4: GND

Table 7

EPO input contact relays

Position Name

Description

J28.1

EPO_NC

EPO activated when opened to J28.2

J28.2

EPO_NC

EPO activated when opened to J28.1

J28.3

EPO_NO

EPO activated when shorted to J28.4

J28.4

EPO_NO

EPO activated when shorted to J28.3

NOTE
The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass.

It does not internally disconnect the input power supply. To disconnect ALL power to the UPS,

open the upstream feeder breaker(s) when the remote EPO is activated.

NOTE
Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor

board and must remain installed if using NC contacts.

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm

2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

Advertising