4 dual bus system, 1 cabinet installation, 2 external protective devices – Liebert Emerson NX UPS System User Manual

Page 39: 3 power cables, Dual bus system, Cabinet installation, External protective devices, Power cables

Advertising
background image

UPS Multi-Module Installation

31

3.4

Dual Bus System

3.4.1 Cabinet Installation

The Dual Bus System consists of two independent UPS configurations each consisting of one or more

UPS modules. Dual Bus Systems are high availability configurations suitable for loads with multiple

input terminals. For single input loads an optional Static Transfer Switch may be added and the stan-

dard Load Bus Synchroniser activated. Depending on the configuration, follow the appropriate instal-

lation instructions for each system.
Place the UPS modules side by side and interconnect as shown below.
The objective of the Dual-bus Synchronizer (DBS) is to keep the output of two independent UPS sys-

tems (or parallel systems) in synchronization. One system is designated as the master; the other is

designated as the slave. The operating modes covered comprise master and or slave operating

inverter or bypass mode.

Figure 18 Typical dual bus system configuration with static transfer switch and Load Bus Synch

3.4.2 External Protective Devices

Refer to the instructions supplied in 1.0 - Single Module UPS Installation.

3.4.3 Power Cables

The wiring of power cables is similar to that of single module system. The Bypass and the Main input

sources must be referenced to the same neutral potential and input earth leakage monitoring devices,

if installed, must be located upstream of the common neutral sinking point. Refer to the instructions

in 1.0 - Single Module UPS Installation

Input

Rectifier

UPS1

Bypass

supply

Input

Rectifier

UPS 6

Intermodule

control cable

STS

LBS

Load

Intermodule

control cable

Bypass

supply

Input

Rectifier

Input

Rectifier

UPS 6

UPS1

Advertising