6 emergency shutdown with epo, 7 auto restart, Emergency shutdown with epo – Liebert Emerson NX UPS System User Manual

Page 58: Auto restart, Warning

Advertising
background image

Operating Procedures

50

6.6

Emergency Shutdown With EPO

This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The

system will turn off the rectifier, inverter and stop powering the load immediately (including the

inverter and bypass), and the battery stops charging or discharging.
If the input utility is present, the UPS’s controls will remain active; however, the output will be

turned off. To remove all power from the UPS, the external feeder breaker should be opened.

6.7

Auto Restart

When the main and bypass sources fail, the UPS draws power from the battery system to supply the

load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it

will shut down.
The UPS will automatically restart and enable output power:

• After utility power is restored
• If “Auto Recovery after EOD Enabling” is enabled
• After the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes).

If the “Auto Recovery after EOD Enabling” feature is disabled, the user may restart the system man-

ually by pressing “Fault Clear” button.

6.8

Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions

Once all appropriate measures have been taken to correct the problem indicated by the alarm mes-

sage appearing on the operator control panel display, carry out this procedure to restore the UPS to

regular operation following an EPO action or for the following reasons: Inverter Overtemperature,

Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.
When the user confirms that the fault is cleared:
1. Press the FAULT CLEAR button to let the system exit the Emergency Off state.
2. Press the INVERTER ON button on the right side of the operator control panel for longer than

2 seconds.

After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely.

When input utility is returned, if the rotary switch (SW1) is in either Bypass or in Normal position,

the UPS will start up on Bypass. There will be power at the output terminals of the UPS.

NOTE
The rectifier will start again, and the bypass will begin to power the load (for units with

internal battery contactor installed, the battery contactor will close). The Rectifier indicator

flashes while the rectifier is starting up. When the rectifier enters the normal operation state

(about 30 seconds), the rectifier indicator turns green.

NOTE
The rectifier will be turned On automatically when the overtemperature fault disappears at

5 minutes after the disappearance of overtemperature signals.

!

WARNING

If the rotary switch is in the Maint. position and input utility is present, there will be power at

the output terminals of the UPS.

Advertising