Safety precautions, Conformity and standards, Warning – Liebert Emerson NX UPS System User Manual

Page 9

Advertising
background image

1

SAFETY PRECAUTIONS

This manual contains information concerning the installation and operation of this Emerson Network

Power Liebert NX

Uninterruptible Power System (UPS).

This manual should be read before commencing installation.
The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or

agent).
Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of war-

ranty.
The Liebert NX has been designed for Commercial/Industrial use only, and is not recommended for

use in life support applications.
This is a low emission CLASS A Uninterruptible Power System (UPS) product. In a residential envi-

ronment, this product may nevertheless cause radio interference, in which case, the user may be

required to take additional measures.

Conformity and Standards

This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Aus-

tralia and New Zealand EMC Framework (C-Tick) and with the following product standards for Unin-

terruptible Power System (UPS).

• EN / IEC / AS 62040-1-1—General and safety requirements for use in operator access area
• EN / IEC / AS 62040-2—EMC requirements; Class A compliant
• EN / IEC / AS 62040-3—Performance requirements and test methods

For more details, see 9.0 - Technical Specifications
Continued compliance requires installation in accordance with these instructions and the use of man-

ufacturer approved accessories only.

!

WARNING

High Leakage Current
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
Earth leakage current exceeds 3.5 mA and is less than 860 mA.
Transient and steady-state earth leakage currents, which may occur when starting the

equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional

pulses (class A) and insensitive to transient current pulses.
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.
This equipment must be earthed in accordance with the local electrical code of practice.

!

WARNING

Back-Feed Protection Notice
This UPS is fitted with a voltage-free contact closure signal for use with an external

automatic disconnect device (supplied by others) to protect against back-feeding voltage into

the bypass input. If this signal is not used by the installer, a label must be added at the

external bypass input disconnect device to warn service personnel that the circuit is

connected to a UPS.
The text to use is the following or equivalent:
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS

CIRCUIT.