Single Module UPS Installation

14

1.8.4 Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)

Figure 5

Output dry contacts and EPO wiring

Table 6

Output dry contact relays

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay; normally open; closed when bypass SCR is shorted

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay; normally closed; open when bypass SCR is shorted

J21.2

INV_O

Inverter mode relay; normally open; closed when UPS is in inverter mode

J21.3

INV_S

Inverter mode relay center

J21.4

INV_C

Inverter mode relay; normally closed. Opened when UPS is in inverter mode

J25.2

ACF_O

Main input fault relay; normally open. Closed when main input is in fault

J25.3

ACF_S

Main input fault relay center

J25.4

ACF_C

Main input fault relay; normally closed. Open when main input is in fault

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm

2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

EPO - NC

EPO - NO