Single Module UPS Installation
14
1.8.4 Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)
Figure 5
Output dry contacts and EPO wiring
Table 6
Output dry contact relays
Position
Name
Description
J13.2
BFP_O
Bypass feedback protection relay; normally open; closed when bypass SCR is shorted
J13.3
BFP_S
Bypass feedback protection relay center
J13.4
BFP_C
Bypass feedback protection relay; normally closed; open when bypass SCR is shorted
J21.2
INV_O
Inverter mode relay; normally open; closed when UPS is in inverter mode
J21.3
INV_S
Inverter mode relay center
J21.4
INV_C
Inverter mode relay; normally closed. Opened when UPS is in inverter mode
J25.2
ACF_O
Main input fault relay; normally open. Closed when main input is in fault
J25.3
ACF_S
Main input fault relay center
J25.4
ACF_C
Main input fault relay; normally closed. Open when main input is in fault
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
EPO - NC
EPO - NO
X2
X1
BFP_C
J21
J25
J28
BFP_
S
BF
P_
O
INV_O
INV_
S
INV_
C
AC
F
_
C
ACF_
S
AC
F_O
J13
+12V