UPS Multi-Module Installation

26

3.0

UPS M

ULTI

-M

ODULE

I

NSTALLATION

3.1

General

The installation of a multi-module UPS configuration must follow the installation procedure for a sin-

gle UPS module with the additional requirements detailed in this chapter.
In addition to the local EPO push button on the front panel of the UPS module (that stops operation of

that module), the UPS supports also a remote emergency stop to permit simultaneous multi-module

shutdown.

Figure 13 Emergency power off connections

NOTES
1. The remote emergency power off switch must be voltage-free and Normally Open or

Normally Closed.
2. The open voltage supplied is 12VDC, < 20mA
3. This external emergency stop may be supplied with a second set of contacts that can be used

to trip incoming mains or bypass supply circuit breakers supplied by others and fitted with

remote trip units.
4. Normally Closed EPO - X2: 1&2, these terminals are supplied factory-linked on the monitor

board.

UPS2

UPS1

Monitor Board

Monitor Board

X2:1
X2:2

X2:1
X2:2

EPO

UPS1

X2:3

X2:4

Monitor Board

UPS2

X2:3
X2:4 Monitor Board

EPO