Options—For Assembly Inside the UPS Cabinet

71

8.2

OC485 Web Card – Modbus, Jbus, IGM Net

The OpenComms 485 Card facilitates SiteScan Web or Building Management Systems monitoring.
The RS232 port is used for connection to a personal computer for setting up.
The RS-485 port supports IGM Net and Modbus/JBus protocols and maps the operation of the UPS

including status, alarms and data (voltages, currents, frequency, power, power factor, temperatures

etc.)

Figure 42 OC485 Web card

8.2.1 Remote Alarm Monitor

Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel that is

driven by volt-free alarm status contacts from an optional relay alarm board.

Table 28

NX communication options

Physical

description

of port

Labeled

ID Name

of Port

On the UPS

LCD screen,

under Settings,

controlled by:

Monitoring

Devices

supported

Baud

rate

Comments

Top

Intellislot

Intellislot 2

(On Monitor Board)

Comm 1

Multiport 4

any

Relaycard-int

any

OCWEB-LB

2400

Not simultaneous with

Multilink in RS232-1

Modbus/Jbus

2400

Middle

Intellislot

Intellislot 1

(On Monitor Board)

Comm 2

Multiport 4

any

Relaycard-int

any

OCWEB-LB

2400

Not simultaneous with

Multilink in RS232-2

Modbus/Jbus

2400

Bottom

Intellislot

Intellislot 3

(On Monitor Board)

Comm 3

Multiport 4

any

Relaycard-int

any

OCWEB-LB

2400

Modbus/Jbus

2400

Top

DB9 port

RS232-1

Comm 1

Multilink Serial

9600

Not simultaneous with Web

card in top Intellislot.

Bottom

DB9 port

RS232-2

Comm 2

Service Software

(Reserved)

9600

Not simultaneous with Web

card in middle Intellislot.