Options—For Assembly Inside the UPS Cabinet

67

8.1.2 Redundant Fan for Power Module

In addition, to ensure sufficient cooling power at various operation modes with 100% rated load, a

redundant power module fan set can be supplied, thus ensuring continuity of UPS operation even

with the failure of some fans. No extra footprint is required.

Figure 37 Redundant power module fan set

Figure 38 Communication bays and cable location

Fan120

Fan120

Fan120

Fan120

(AC Fan 1-4)

(AC Fan 1-3)

(AC Fan 1-2)

(AC Fan 1-1)

Redundant AC Fan

TOP VIEW

Standard AC Fan

Notes:

a) All Intellislot cards are supported in any bay.

b) Port sharing is:

- PERMITTED between RS232-x DB9 devices and Relay /

Multiport4 Intellislot cards (i.e., Serial Multilink software

will work from RS232-1 DB9 also when relay card is

inserted in the top bay.

- NOT PERMITTED between RS-232-x D-B9 devices and

OCWeb / OC485 cards (i.e., Serial MultiLink software will

not work from RS232-1 DB-9 when OCWeb card is inserted

in the top bay.

RS-232-1 DB-9 (COM Port 1) - Serial MultiLink Software

(Port Setting 2400 Baud)

RS-232-2 DB-9 (COM Port 2 - Service Access Software

(Port Setting 9600 Baud)

Top Bay

Mid Bay

Bottom Bay

Relay Card (no port setting required)

Multiport4 (no port setting required)

OCWeb LB / OC485 (port setting 2400 Baud)

Suggested routing of customer-supplied

communication cables

Gland plate for cable exit

DB-9

Monitor

Board

Top

Mid

Preferred Device This Location

Location

Bottom

Location

Preferred Device This Location