Technical Specifications

74

Table 32

Mechanical characteristics

Rated Power, kVA

Unit of

Measurement

10

15

20

30

Dimensions, WxDxH

mm (in)

600x700x1400

(23-9/16x27-5/8x55)

Mass

Mass without batteries

kg (lb)

180 (397)

204 (450)

204 (450)

210 (463)

Finish

N/A

Pantone 877 (Silver grey)

equivalent Becker Silver epoxy polyester powder 041-37-2

Protection Degree, IEC (60529)

N/A

IP20 (finger-proof with front doors open or closed)

Table 33

Rectifier AC input (mains)

Rated Power, kVA

Unit of

Measurement

10

15

20

30

Rated AC Input Voltage

1

VAC

380/400/415

(3-phase and sharing neutral with the bypass input)

Input Voltage Tolerance

2

VAC

305V to 477V

304V to 208V (output derated below 70%)

Frequency

2

Hz

50/60Hz (tolerance 40Hz to 70Hz)

Power Factor

kW/kVA, full

load

(half load)

0.99 (0.98)

Input Power

kVA rated

3

(maximum

4

)

8.9 (11.7)

13.3 (18.9)

17.8 (23.3)

26.6 (35.0)

Input Current

A rated

3

(maximum

4

)

12.9 (16.9)

19.3 (27.4)

25.8 (33.8)

38.6 (50.7)

Harmonic Current Distortion

THDI % FL

3

3

3

3

Duration of Progressive

Power Walk-In

sec

10 seconds to reach full rated current

(selectable 5 through 30 seconds in 5-second intervals)

1. Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged

battery

3. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charged
4. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.