Technical Specifications

73

9.0

T

ECHNICAL

S

PECIFICATIONS

9.1

Conformity and Standards

The UPS has been designed to conform to the following European and international standards:

The product standards in Table 29 incorporate relevant compliance clauses with generic IEC and EN

standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000

series) and construction (IEC/EN/AS60146 series and 60529).

Table 29

Compliance with European, international standards

Description

Normative reference

General and safety requirements for UPS used in

operator access areas

EN 50091-1-1 /IEC 62040-1-1 / AS 62040-1-1

Electromagnetic compatibility (EMC) requirements for

UPS

EN 50091-2 / IEC 62040-2 / AS 62040-2 (Class A)

Method of specifying the performance and test

requirements of UPS

EN 50091-3 / IEC 62040-3 / AS 62040-3 (VFI SS 111)

Table 30

Environmental characteristics

Rated power, kVA

Unit of

Measurement

10

15

20

30

Acoustic Noise Level at 1 Meter (39 in)

dBa

51.0

51.5

51.6

56

Altitude of Operation

m (ft)

≤1000m (3280 ft) above sea level

de-rate power by 1% per 100m(328 ft) between

1000 and 2000 m (3280 and 6560 ft)

Relative Humidity

-

0 to 95% non condensing

Operating Temperature

°C (°F)

0 to 40 (32-104°)

Battery life is halved for every 10° (18°) increase

above 20° (68°)

Storage-Transport Temperature for UPS

°C (°F)

-20 to 70 (-4 to 158)

Recommended Battery Storage

Temperature

°C (°F)

-20 to 30 (-4 to 86)°F)

(20°C [68°F] for optimum battery storage)

Table 31

Overall

efficiency, heat losses and air exchange

Rated Power, kVA

Unit of

Measurement

10

15

20

30

Normal Mode (dual conversion)

%

90.4

91.2

91.3

91.9

ECO Mode

%

93.2

94.2

94.7

96.6

Inverter Efficiency (DC/AC)

(battery at nominal voltage 480VDC and full-rated linear load)

Rated Power,

kVA

10

15

20

30

Battery Mode

%

91.3

91.7

92.0

92.5

Heat Loss & Air Exchange (Ventilation)

Rated Power

kVA

10

15

20

30

Normal Mode

kW

1.6

1.8

2.2

2.6

ECO Mode

kW

1.3

1.4

1.4

1.5

No Load

kW

1.3

1.3

1.3

1.3

Maximum Forced Air Cooling (front intake, back exhaust)

L/sec (m

3

/hr)

119

(428)

239 (860)

Input and output voltage 400VAC, battery charged, full rated linear load