Operator Control Panel and Display

63

Fault Reset

Fault clear direct access key pressed

Alarm Silence

Silence On/Off direct access key pressed

Turn On Fail

Inverter failed to turn on when Inverter On direct access key was pressed. This may be as a

result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready.

Alarm Reset

Fault clear or Silence On/Off direct access key pressed

Bypass Mode

Load supplied from AC input bypass supply.

Normal Mode

Load supplied from Inverter output through double conversion of the AC mains input supply.

Battery Mode

Load supplied from Inverter output through double conversion of the Battery supply.

Source share mode

Load supplied from Inverter output through shared double conversion of the AC mains input

supply and of the Battery supply.

UPS Shutdown

UPS Shutdown, output power-down

Check UPS Output

Inverter off during normal startup (diagnostics information only)

Generator Connected

Generator active signal received. Source share mode may be activated pending UPS settings.

BCB open

Battery Circuit Breaker status (open)

BCB closed

Battery Circuit Breaker status (closed)

Battery Float Charging

Battery status (Float charge mode)

Battery Boost Charging

Battery status (Boost charge mode)

Battery Discharging

Battery status (discharge mode)

Battery Period Testing

Automatic periodic battery maintenance discharge test (20% capacity discharge)

Batt. Capacity Testing

User initiated battery capacity discharge test (100% capacity discharge)

Batt. Maint. Testing

User initiated maintenance discharge test (20% capacity discharge)

UPS System Testing

User initiated UPS self test

Inverter in Setting

Inverter starting up and synchronising

Rectifier in Setting

Rectifier starting up and synchronising

MBP-T cabinet Fan Fault

Maintenance bypass cabinet fans fault.

Ext Input TX Overtemp

External Input Isolation Transformer Over Temperature

Ext Output TX Overtemp

External Output Isolation Transformer Over Temperature

Battery Room Alarm

Environment in Battery Room Needs Attention

Rotary Sw. Test Pos.

Rotary switch is in test position.

Rotary Sw. Normal Pos.

Rotary switch is in normal position.

Rotary Sw. Bypass Pos.

Rotary switch is in bypass position.

Rotary Sw. Maint. Pos.

Rotary switch is in maintenance position.

Battery Contactor Open

Battery Contactor Open

Battery Contactor Close

Battery Contactor Closed

Battery Reverse

Connect the battery again and check the wiring of batteries

No Battery

Check the battery and the wiring of batteries

Auto start

After UPS was shutdown at EOD, inverter auto starts when utility restore

Rec. Flash Update

Rectifier firmware is being update

Inv. Flash Update

Inverter firmware is being update

Monitor Flash Update

Monitor firmware is being update

Input contactor fault

Input contactor is in fault

Contactor P.S. 1 fault

Contactor Power Supply board 1 Fault

Contactor P.S. 2 fault

Contactor Power Supply board 2 Fault

LBS abnormal

LBS is abnormal

DSP firmware error

The inverter firmware does not match with the rectifier firmware.

Table 22

UPS messages (continued)

Message

Description / Suggested Action (if any)