Operator Control Panel and Display

59

System

Sout (kVA)

Sout: Apparent power

Pout (kW)

Pout: Active power

Qout (kVAR)

Qout: Reactive power

Single unit, no parallel data When configured as a single unit, UPS has only native load, no system

load.

Battery

Battery voltage (V)

Battery bus voltage

Battery current (A)

Battery bus current

Battery temperature (°C)

Internal battery temperature °C

Remain Time Min.

Battery run time remaining

Battery boost charging

Battery is boost charging

Battery float charging

Battery is float charging

Battery disconnected

Battery is not connected

Records

(history log)

Displays all records in the history log

Language

(choices for text displayed) User may select any of 12 languages for LCD text.

Settings

Display contrast

Adjust the LCD display contrast

Date format set

Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D

Date & time

Set the date and time

Comm1 baud rate

Communication baud rate setting for Intellislot 1

Comm2 baud rate

Communication baud rate setting for Intellislot 2

Comm3 baud rate

Communication baud rate setting for Intellislot 3

Communication address

This setting is applicable to RS485 communication mode

Communication mode

Communication Mode Setting

Callback times

When Intellislot 1 Communication mode is Modem, this parameter sets

the number of times a number is redialed to send an alarm notification.

Phone No.1

When Intellislot 1 Communication mode is Modem, this is the first phone

number to be dialed (to send an alarm notification).

Phone No.2

When Intellislot 1 Communication mode is Modem, this is the second

phone number to be dialed (to send an alarm notification).

Phone No.3

When Intellislot 1 Communication mode is Modem, this is the third phone

number to be dialed (to send an alarm notification).

Command password

User can modify the command password.

Command

(start/stop

battery &

system

tests)

Battery maintenance test

This test performs a partial discharge of the battery to obtain a rough

estimate of the battery capacity. Load must be between 20% and 100%.

Battery capacity test

This test performs a full discharge of the battery to obtain a precise

measure of the battery capacity. Load must be between 20% and 100%.

System test

This is a self-test of the UPS. When the user activates this function, a pop-

up window appears about 5 seconds later to show the results.

Stop testing

Manually stops a battery maintenance test, battery capacity test or system

test.

Freshening Charge

This command will allow a temporary Equalize charge for the batteries.

This charge is configurable for 1 to 36 hours

Stop Freshening Charge

Manually stop a Freshening Charge

Version

UPS version

Provides UPS firmware version numbers for the inverter, rectifier and

software display board.

UPS model

Provides UPS model information—for example, 400V-50Hz.

Table 21

Descriptions of UPS menus and data window items (continued)

Menu

Type

Item Type

Explanation