Liebert Emerson NX UPS System User Manual

Page 69

Advertising
background image

Operator Control Panel and Display

61

Bypass Abnormal

This alarm is triggered by an inverter software routine when the amplitude or frequency of

bypass voltage exceeds the limit.

This alarm automatically resets once the bypass voltage goes normal.

First check if there are some relevant alarms such as “Bypass disconnect open”, “Bypass phase

reverse” and “Mains neutral lost”. If they appear, solve them first.

1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass

limit. Note here the rated voltage and frequency are specified by “Output voltage level” and

“Output frequency level” respectively.

2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and

frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If

the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger

through the configuration software according to the customer’s agreement.

Inverter Asynchronous

This alarm is triggered by an inverter software routine when the inverter and bypass waveforms

are misaligned by more than 6 degrees in phase. This alarm resets automatically once the

condition is no longer true.

1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it

first.

2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and

seek any possible measurements.

Inverter Fault

Inverter output voltage beyond limits. Load transfers to bypass.

Inverter Overtemp.

The temperature of the inverter heat sink is too high to keep inverter running.

This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter

bridge heat sink.

The UPS will recover automatically after a 5 minute delay from the disappearance of the

overtemperature signal.

If the overtemperature condition is true, then check for and verify:

1. high ambient air temperature.

2. blocked cooling airway.

3. any fan failure.

4. prolonged inverter overload

Fan Fault

At least one of the cooling fans has failed

Inverter STS Fail

At least one of the static switches of inverter side is open or short circuit. This fault is locked until

power off.

Bypass STS Fail

At least one of the static switches of bypass side is open or short circuit. This fault is locked until

power off

Operation Invalid

This record is registered following an incorrect operation:

Output Fuse Fail

At least one of the inverter output fuses is blown. Inverter shuts down. Load transfers to bypass.

Control Power 2 Fail

UPS operates but Redundant Control Power is not available.

Unit Over load

The UPS is confirmed to be overload when the load arises above 105% nominal rating.

The alarm automatically resets once the overload condition is removed.

1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to

determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing

error can also leads to the alarm.

System Over load

The UPS parallel system is confirmed to overload when the total load arises above 105%

nominal rating for the set basic number of UPSs. The alarm automatically resets once the

overload condition is removed.

1. Confirm that the alarm is true by checking the system load percent indicated on the LCD

panel to determine which phase is being overloaded.

2. If the alarm is true, measure the actual output current to verify that the indications are valid.

Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing

error can also leads to the alarm.

Table 22

UPS messages (continued)

Message

Description / Suggested Action (if any)

Advertising