1.8.3 External Circuit-Breaker Interface
J10 is the interface to any external battery circuit breaker (BCB).
Figure 4
Jumper connection for BCB interface
Table 5
External circuit-breaker interface
Position
Name
Description
J10.1
DRV
BCB Driver Signal - (reserved)
J10.2
FB
BCB Contact State -(reserved)
J10.3
GND
Power Ground
J10.4
OL
BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
UPS Monitoring Board
J10
OL
DR
V
GN
D
FB
Battery Circuit Breaker
OL
Aux – N.O.
Aux – N.O.