16 Room Air Conditioner

Piping Length and Elevation

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

A

Oil trap

Outdoor unit

Indoor unit

B

If piping length is more than 16.4ft(5m)

CAUTION: Capacity is based on standard length and maximum allowance length is
on the basis of reliability.
Oil trap should be installed every 16.4~23feets (5~7 meters).

Installation

Pipe Size

Capacity

(Btu/h)

Suction

Evap

Max.

length

A

m(ft)

Additional

Refrigerant

g/m(oz/ft)

Max.

Elevation

B

m(ft)

Standard

Length

m(ft)

9k, 12k

Ø12.7mm(1/2") Ø6.35mm(1/4")

7.5(25)

7.5(25)

15(49)

20(0.22)