Service Manual 65

Troubleshooting Guide

Compressor/Outdoor Fan are unable to drive.

Turn on Main Power

Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 2°F at least.

When in Fan Mode, Compressor/Outdoor Fan is stopped.

Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).

When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.

• Check the related circuit of R02H(12.1K), R04H(6.2K), Micom (No.27)

(Indoor unit).

• Check the indoor temperature sensor is disconnected or not(About 10k

/ at 77°F).

When the temperature around Outdoor PWB Ass'y is above 163°F the
compressor is stop and only Outdoor Fan is operating.

Turn off Main Power

• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of Compressor/Outdoor

Fan Motor.

Check Relay(RY - COMP) for driving compressor.

• When the power(About AC200V) is applied to the connecting wire termi-

nal support transferred to compressor, PWB Ass'y is normal.

• Check the circuit related to the relay(Outdoor unit).

Check point

COMP ON

COMP OFF

Between Micom(No.

DC5V

DC0V

5, 6) and GND

Between IC01M, IC02M(No. 9)

Below DC 1V

About DC12V

and IC01M, IC02M(No. 8)

(app)