Charging, Example, Important – LG LA120CPI User Manual

Page 31

Advertising
background image

Service Manual 31

Air purgingd

Charging

Each outdoor unit is factory charged (nameplate charge) for the evaporator as well as a 7.5m(25ft) line set.
Any time a line set is used either shorter or longer then the nominal 7.5m(25ft) line set length the refrigerant
charge has to be adjusted.

Whether the line set is made shorter or longer you must adjust the charge based on how many ft of tubing are
either added or removed based on 20g(0.22oz) of R-410A per meter(foot).

Example:

A 30ft line set is used
5 additional ft X 0.22 ounce per foot= add 1.1 ounces of R-410A

Important:

If you are ever uncertain of the unit charge, reclaim, evacuate and weigh in the correct charge using the unit
nameplate charge adjusting for line sets longer or shorter than 7.5m(25ft).

Confirm the refrigerant R-410A. Use manifold gauge and hose for R-410A.

Pipe Size

Capacity

(Btu/h)

Suction

Evap

Max.

length

A

m(ft)

Additional

Refrigerant

g/m(oz/ft)

Max.

Elevation

B

m(ft)

Standard

Length

m(ft)

9k, 12k

Ø12.7mm(1/2") Ø6.35mm(1/4")

7.5(25)

7.5(25)

15(49)

20(0.22)