Flaring work and connection of piping

Flaring work and connection of piping

Flaring Work

Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure.

Cutting the pipes and the cable.

1. Use the piping kit accessory or the pipes purchased

locally.

2. Measure the distance between the indoor and the

outdoor unit.

3. Cut the pipes a little longer than measured distance.

4. Cut the cable 4.9ft(1.5m) longer than the pipe length.

Removing burrs

1. Completely remove all burrs from the cut cross section

of pipe/tube.

2. Put the end of the copper tube/pipe in a downward

direction as you remove burrs in order to avoid dropping
burrs into the tubing.

Putting nut on

• Remove flare nuts attached to indoor and outdoor unit,

then put them on pipe/tube having completed burr
removal.
(not possible to put them on after flaring work)

Flaring work

1. Firmly hold copper pipe in a die in the dimension shown

in the table below.

2. Carry out flaring work with the flaring tool.

Copper

pipe

90

°

Slanted Uneven Rough

Pipe

Reamer

Point down

Flare nut

Copper tube

mm

inch

mm

Ш6.35

1/4

1.1~1.3

Ш9.52

3/8

1.5~1.7

Ш12.7

1/2

1.6~1.8

Ш15.88

5/8

1.6~1.8

Ш19.05

3/4

1.9~2.1

Outside diameter

A

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A"