Service Manual 59

Troubleshooting Guide

2. Evacuation

(All amount of refrigerant leaked)

• Procedure

(1) Connect the vacuum pump to the center hose

of charge set center hose

(2) Evacuation for approximately one hour.

– Confirm that the gauge needle has moved

toward -76 cmHg (vacuum of 4 mmHg or less).

(3) Close the valve (Lo side) on the charge set,

turn off the vacuum pump, and confirm that
the gauge needle does not move (approxima-
tely 5 minutes after turning off the vacuum
pump).

(4) Disconnect the charge hose from the vacuum

pump.
– Vacuum pump oil.

If the vacuum pump oil becomes dirty or
depleted, replenish as needed.

Lo

Open

Open

Vacuum pump

3-Way
valve

Outdoor unit

Liquid side

Indoor unit

Gas side

3-Way
valve

CLOSE

OPEN