The function of main control

INTAKE AIR TEMP.

SETTING TEMP. +1°F
(Compressor ON)

SETTING TEMP. -1°F
(Compressor OFF)

Setting
fan speed

Setting
fan speed

More than

3 minutes

More than

3 minutes

Setting
fan speed

COMPRESSOR

ON

OFF

ON

OFF

ON

INDOOR FAN SPEED

Low

Low

Protection of the indoor heat exchanger from frosting

• Compressor and outdoor fan stop when indoor pipe temperature is below 32°F(0°C) and restart at the pipe

temperature is above 45°F(7°C).

3. Cooling Operation Mode

• When selecting the Cooling(

) Mode Operation, the unit will operate according to the setting by the

remote control and the operation diagram is shown below.

CLOSED

OPEN

< Cooling Mode >

8

°

CLOSED

OPEN

< Heating Mode >

8

°

1. Time delay Safety Control

• 3min.; The compressor operation is delayed for 3 minutes to balance the pressure of cycle.

(Protection of compressor)

• 5sec.; The indoor fan is delayed for 5 seconds, when operating initially, to prevent noises occurred by the vertical

louver and wind.

• 2min.; The reversing valve is delayed for 2 minutes to prevent the refrigerant-gas for abnormal noise when the

heating operation is OFF or switched to the other operation mode while compressor is off.
While compressor is running, it takes 3~5 seconds to switch.

2. Chaos Swing Mode

• By the Chaos Swing key input, the vane automatically operates with the Chaos Swing or they are fixed to the

desired direction.

• While in Chaos Swing mode, the angles of cooling and heating cycle operations are different.