When vertical louver does not operate, Service manual 67 troubleshooting guide – LG LA120CPI User Manual

Page 67

Advertising
background image

Service Manual 67

Troubleshooting Guide

When Vertical Louver does not operate.

• Confirm that the Vertical Louver is normally geared with the shaft of

Stepping Motor.

• If the regular torque is detected when rotating the Vertical Louver with

hands

Normal

• Check the connecting condition of CN-UP/DOWN Connector
• Check the soldering condition(on PWB) of CN-UP/DOWN Connector

Check the operating circuit of the Vertical Louver

• Confirm that there is DC +12V between pin

(RED) of CN-UP/DOWN and

GND.

• Confirm that there is a soldering short at following terminals.

- Between

77

,

78

,

79

and

80

of MICOM

- Between

4

,

5

,

6

and

7

of IC02M

- Between

10

,

11

,

12

and

13

of IC01M

- Between

1

,

2

,

3

,

4

and

5

of CN-UP/DOWN

If there are no problems after above checks

• Confirm the assembly conditions that are catching and interfering parts in

the rotation radial of the Vertical Louver

Advertising
This manual is related to the following products: