The phenomena in case of connecting error – LG LA120CPI User Manual

Page 69

Advertising
background image

Service Manual 69

Troubleshooting Guide

The phenomena in case of connecting error

INDOOR UNIT

Connector Type

Condition

Open and connecting error

Open

Open

Open

Open

Short between terminals

(

and

) of ROOM-TH.

Short between terminals

(

and

) of PIPE-TH.

Short between terminals

• The same as the phenomenon of Outdoor Unit.

• The up/down vane does not operate.

• The up/down vane does not smoothly operate.

• It does not operate with a remote controller.

• The operation indicator blinks once

(on for 0.5 second, off for 3 seconds).

• The compressor operates continuously regardless

of the setting temperature and the variation of room
temperature.

• The operation indicator blinks once

(on for 0.5 second, off for 3 seconds)

• Continuous operation

• The operation indicator blinks once.

• The compressor and the outdoor fan stop.
• The indoor fan speed is low.

• The indoor fan does not operate.
• The operation indicator of Indoor unit blinks 8 times.

CN-DC/DC

CN-MOTOR

CN-UP/DOWN

CN-DISP

CN-TH

Blue
Black
Brown
Red

Phenomena

On for 0.5 second

Off for 3 seconds

Advertising
This manual is related to the following products: