40 Room Air Conditioner

Operation

6. Heating Operation Mode(only Heating Model)

The unit will operate according to the setting conditions by the remote controller.
The operation diagram is shown below.

INTAKE AIR TEMP.

SETTING TEMP. +6°F
(Compressor OFF)

SETTING TEMP.
(Compressor ON)

Selecting
fan speed

Selecting
fan speed

A

B

A

minimum

10sec.

minimum

1 min.

minimum

10sec.

COMPRESSOR

ON

OFF

ON

OFF

• A point; While the indoor pipe temperature is higher than 95°F, indoor fan operates at low speed. When the

indoor pipe temperature becomes lower than 95°F, indoor fan stops.

• B point; When the indoor pipe temperature is higher than 100°F(38°C), fan operates at selected fan speed.

INDOOR FAN SPEED

Low

OFF

Low

Low

OFF

OFF

OFF

LOW

ON

Selecting
fan speed

INDOOR PIPE

TEMP.

82°F

78°F

1min

INDOOR FAN SPEED

COMPRESSOR

Hot-Start Control

• The indoor fan stops until the indoor pipe temperature will be reached at 82°F.

• During heating operation, if indoor pipe temperature falls below 78°F fan stops.

• The operation diagram is shown below.