Service Manual 61

Troubleshooting Guide

Additional gas charging

(Gas leakage)

• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal operating suc-

tion pressure.

• Use the graph or the equation below to get operating suction pressure according to indoor and outdoor tem-

perature.

Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.

The method of using graph

- Find outdoor temperature.

- Find indoor temperature onto the curve of outdoor temperature.

- Read suction pressure at the axis of ordinates.

The method of using equation

-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.

13

(At operating the Unit for 10 minutes)

Suction Pressure

(Kg/cm

2

.g)

Outdoor Temp.

C)

Indoor Temp. (˚C)

12

11

10

9

8

7

6

5

5

10

15

20

25

30

35

40

50˚C

40˚C

30˚C

20˚C

10˚C

0˚C

P = 3 + 0.0123 x T

out

1.5

+ 0.8 x T

in

0.5

Where, P

: Suction Pressure(kg/cm

2

.g)

Tout : Outdoor Temperature(˚C)
Tin

: Indoor Temperature(˚C)

Operating Suction Pressure (For R410A)

(According to Indoor & Outdoor Temperature)