Troubleshooting and
Common Questions

Mode Problems

A function block alternates between

Iman

and

Auto

modes.

The status of the input parameter is

Bad::No comm

.

The function block and communication schedules do not have enough time
between them. Complete the following steps:

1.

Edit the schedule to add more time between the function block and
communication schedules. To edit the schedule, double-click the
Schedule icon in the configuration tree.

For more information about editing the schedule, refer to the

View and

Edit a Schedule

section of Chapter 2,

Using the NI-FBUS

Configurator

.

2.

After you edit the schedule, select Configure»Download
Configuration
to download the changes.

For more information about downloading the configuration, refer to
the

Download a Project Configuration

section of Chapter 2,

Using the

NI-FBUS Configurator

.

The PID does not transition to

Auto

mode.

If the status of an

OUT

or

BKCAL_OUT

parameter on an AI or AO block is

Bad::Not Connected

or

Bad::No Comm

, or the downstream block is

not in cascade mode, complete the following steps:

1.

Use the Monitor mode to make sure that the AI and AO blocks are
publishing correct values.

2.

Make sure that the LAS executes the communication schedule. Use
monitoring mode to view the modes, inputs, and outputs of the block.
If the LAS is not executing the schedule, select Configure»Download
Configuration
to download the configuration.