Bkcal_out (process), Bkcal_out_d (process), Block_alm (alarming, diagnostic) – National Instruments NI-FBUS User Manual

Page 77: Block_err (diagnostic), Table 4-10. error codes

Advertising
background image

Chapter 4

Parameters

NI-FBUS Configurator User Manual

4-12

ni.com

BKCAL_OUT (Process)

A back-calculation value published to the

BKCAL_IN

of an upstream block

in a control loop. The

BKCAL_OUT

parameter has the value of the block’s

current output. Before a cascade loop is initialized, the upstream block can
use this value to smoothly transfer to loop control.

BKCAL_OUT_D (Process)

An output value published to an upstream discrete block. The upstream
block can use this value to smoothly transfer to loop control.

BLOCK_ALM (Alarming, Diagnostic)

An alarm parameter used to report error conditions detected within the
block, such as block Out of Service.

BLOCK_ERR (Diagnostic)

A list of error conditions for hardware and software components associated
with the block.

Table 4-10. Error Codes

Error Code

Code

Description

Other

0x0001

Undefined block error condition.

Block Configuration Error

0x0002

The block has detected an error in its
configuration. This usually indicates a
static parameter has been left uninitialized.

Link Configuration Error

0x0004

The logical connection between this block
and another block is misconfigured.

Simulate Active

0x0008

For I/O function blocks, this indicates that
simulation is enabled. For the resource
block, this indicates that the simulate
jumper has been set, allowing simulation to
be enabled in other blocks.

Local Override

0x0010

The block has locally overridden the output
value. This can be the result of an interlock
or faultstate.

Device Faultstate Set

0x0020

The block faultstate behavior is active.