CAS_IN (Process)

A remote setpoint value. If used, will be linked to an output of an upstream
block. In some blocks, may be left unlinked, and a local setpoint value
(typically SP) will be used instead.

CAS_IN_D (Process)

A remote setpoint value. If used, will be linked to an output of an upstream
block. In some blocks, may be left unlinked, and a local setpoint value
(typically

SP_D

) will be used instead.

CHANNEL (I/O, Process)

Used by I/O function blocks to select a physical I/O channel. This mapping
is defined by the manufacturer. In the FP-3000, this parameter is
automatically updated when the

FIELDPOINT_MODULE

and

FIELDPOINT_CHANNEL

parameters are modified.

CLR_FSTATE (Faultstate, Option)

Writing Clear to this parameter causes the device-wide faultstate to be
cleared and output blocks to resume normal execution. Also refer to the

SET_FSTATE

and

FAULT_STATE

parameters.

CONFIRM_TIME (Alarming)

The lower bound on the time the device waits to send alert report messages
if no confirmation is received from a host.

CONTROL_OPTS (Option, Scaling)

A list of options used to adjust the way control blocks, such as the PID
block, operate.

Table 4-11. Control Options

Options

Description

Bypass Enable

If set, lets you set the

BYPASS

parameter and bypass the

algorithm’s control.

SP-PV Track in Man

Causes the setpoint to track the process variable in

Man

.

SP-PV Track in ROut

Causes the setpoint to track the process variable in

ROut

.

SP-PV Track in LO or IMan

Causes the setpoint to track the process variable in

LO

or

IMan

.